HRN-55

The relay protects the sequence and phase failure

It protects the level of undervoltage and overvoltage, including failure/phase sequence in fixed values (undervoltage) 300, (overvoltage) 500V AC

More

3D MODEL
Manufacturer: ELKO EP

Ord. code: 7512 standard
EAN: 8595188137225

Availability: More than 10 pcs
Original price £ 42 -30%
Price excl. VAT £ 29,40
Your price: £ 35.28 incl. VAT
pcs
Quantity
Price excl. VAT
5-9 pcs
£ 27.93
10-24 pcs
£ 27.20
25-49 pcs
£ 26.46
50-99 pcs
£ 24.99
more than 99 pcs
£ 23.52

Description

HRN-55 | Relay for protecting phase sequence and failure

  • replacement for HRN-51 and HRN-51N
  • the relay controls the sequence and phase failures (e.g. checking the correct rotation of motors, drives, etc.)
  • relay designed for monitoring 3-phase networks
  • HRN-55 - power supply from all phases, i.e. that the function of the relay is maintained even in the event of a failure of one of the phases
  • Fixed delay T1 (500ms) and adjustable delay T2 (0.1 - 10s).
  • The faulty state is indicated by LED and output contact of relay is OFF.
  • Output contact: 1x switch 8A / 250V AC1
  • 1-MODULE, DIN rail mounting

                 More information

                • Monitoring terminals: L1, L2, L3
                • Supply and monitored voltage Un: 3x 400V / 50-60Hz
                • Number of contacts: 1x switch (AgNi)
                • Operating position: any
                • Mounting: DIN rail EN 60715
                • Protection degree: IP40 from front panel / IP10 terminals
                • Dimensions: 90 x 17.6 x 64 mm (3.5 x 0.7 x 2.5˝)